EW-60/90 fire curtain system
Fire curtain with low thermal emissivity MFB EW-60/90
Description
The MFB EW-60/90 combines integrity with reduced thermal radiation:
- Fire integrity (E) for [120] minutes at over 1000 °C.
- Thermal radiation limited to ≤ 15 kW/m² for [60] minutes (W).
- Large openings of up to 12,000 × 8,000 mm (width × height).
- Technical textile TECTEX 1120-IT/IN/L2.
- Class E fibreglass base reinforced with Inconel steel.
- Aluminium foil on both sides, which acts as the element that limits thermal radiation.
A curtain exposed to fire heats up and re-emits part of that energy as radiant heat towards the protected side. The aluminium foil on both faces of the TECTEX 1120-IT/IN/L2 textile gives the curtain a low-emissivity surface, which limits the heat radiated from its unexposed face.
Technical diagram
The diagram shows the main dimensions used to size the MFB EW-60/90 system: A – Width: the width of the opening to be protected by the curtain. B – Height: the height of the opening, measured from the floor to the underside of the box. E × F – Box dimensions: the width and height of the box that houses the roller and the rolled-up curtain. H × G – Guide dimensions: the width and depth of the side guides that hold the edges of the curtain. The tables below show the maximum width (A) and height (B) for each box and guide series, together with their dimensions (E × F and H × G, in mm). I'm interested
| BOX | MAXIMUM DIMENSIONS | BOX DIMENSIONS (E/F) mm | |
| WIDTH (A) mm | HEIGHT (B) mm | ||
| SERIE-S22 | 4500 | 3500 | 220x220mm |
| SERIE-S24 | 4500 | 7000 | 240x260mm |
| BOX | MAXIMUM DIMENSIONS | BOX DIMENSIONS (E/F) mm | |
| WIDTH (A) mm | HEIGHT (B) mm | ||
| SERIE-R22 | 12000 | 3500 | 220x220mm |
| SERIE-R24 | 12000 | 6500 | 240x260mm |
| SERIE-R26 | 12000 | 8000 | 260x300mm |
| GUIDES | WIDTH (A) mm | HEIGHT (B) mm | BOX DIMENSIONS (E/F) mm |
| SG-120 | 12000 | Up to 4500 | 70x120mm |
| SG-130 | 12000 | > 4500 | 70x130mm |
Frequently asked questions
-
A fire curtain whose surface limits the radiant heat emitted towards the protected side during a fire. This is the W (radiation) performance, which is added to integrity (E).
-
E curtains provide integrity: they stop flames and hot gases. EW curtains add a limit on thermal radiation. EI curtains add thermal insulation. The MFB EW-60/90 is an EW solution, so compared with an E curtain its distinguishing feature is reduced thermal radiation.